RLS-12B SF6 load break switch
General:RLS-12B an indoor high-voltage SF6 load switch, an switchgear with the rat…
RLS-12B SF6 load break switch

RLS-12B SF6 load break switch

Detailed description

  • Description
  • Technical data

General:
RLS-12B an indoor high-voltage SF6 load switch, an switchgear with the rated voltage of 12kV/24kV, adopted with SF6 gas as an arc-extinguishing and insulation medium, including thethree contactors for switching-on and switching-off andto-ground, and is characteristic in its small volume, its convenient installation and operation and itsthe great adaptability with surroundings. 
RLS-12 of an indoor high-voltage SF6 load switch and RLS-12B of SF6 load switch plus fuse combination canfunctionto protect and controlthe electric equipmentsfor power supply and transformer substations especially being suitable for ring net cabinet, cable branch cabinet and distribution switching substation. 
RLS-12 of an indoor high-voltage SF6 load switch and RLS-24B load switch plusfuse combination are complied withthe standards of GB3804-1990, IEC60256-1,1997, GB16926, IEC60420 etc.. 


Service environment:
a) Airtemperature 
Maximumtemperature: +40℃; Minimumtemperature:-5℃
b) Humidity:  Monthly average humidity 95%; Daily average humidity 90%. 
c) Altitude above sea level    Maximum installation altitude: 2500m 
d) Ambient air not apparently polluted by corrosive and flammable gas, vapor etc. 
e) Nofrequent violent shake



Note: For short circuit breaking and peak current isbased on Fuseplus combination.

No


Item

Unit

Parameter

1

Rated voltage

kV

12

2

Rated frequency

Hz

50/60

3

Rated current

A

630/800

4

wet

1min Power frequency  withstand voltage
dry

kV

38

 

48

5

Lightning impulse withstand voltage

kV

75

6

Rated short circuit breaking current (peak)

kA

80

7

Rated activeload and close circuit breaking current

A

63

8

Rated transferring current

A

1700

9

Rated short circuit making current (peak)

kA

80

10

Rated cable(line) charging breaking current

A

50 and 10

1 1

Cable charge breaking current in earthing fault

A

20

12

Rated withstand current (peak)

kA

80

13

Short time withstand current (2s)

kA

31.5

14

Mechanism life

times

5000

Best solution for your power!